伟信医药
GREAT INNOVATION PHARMA

 To Be An  Excellent Brand of

Pharmaceutical  Intermediates Manufacturer in the world

  • 1
  • 2
  • 3
  • 4
Noise, boiler exhaust, unorganized waste gas, sewage treatment station exit detection
2018-4-28
source:unknown
clicks:  2247        作者:未知
  • Noise, boiler exhaust, unorganized waste gas, sewage treatment station exit detection

    Table 3 unit of noise detection in the factory: dB (A)

    Monitoring point position

    Monitoring date

    Daytime noise

    Nocturnal noise

    For the first time

    The second time

    For the first time

    The second time

    1#

    2017.12.4

    Fifty-three point four

    Fifty-three point six

    Forty-eight point three

    Forty-eight point seven

    2#

    Forty-nine point three

    Forty-eight point eight

    Forty-six point nine

    Forty-six point three

    3#

    Forty-nine point seven

    Forty-nine point one

    Forty-six point eight

    Forty-six point nine

    4#

    Fifty point one

    Fifty point nine

    Forty-seven point five

    Forty-seven point six


    Boiler exhaust gas test results (sampling date: 2017.12.4)

    Detection project

    Company

    detection result

    For the first time

    The second time

    Third time

    SO2

    Measured concentration

    Mg/Nm3

    Three

    Three

    Four

    Conversion concentration

    Mg/Nm3

    Eight point two

    Seven point eight

    Nine point six

    Emission

    Kg/h

    Zero point zero five six

    Zero point zero five nine

    Zero point zero six eight

    NOX

    Measured concentration

    Mg/Nm3

    Forty

    Forty-two

    Forty-four

    Conversion concentration

    Mg/Nm3

    Eighty-one point eight

    One hundred and nine point six

    One hundred and five point six

    Emission

    Kg/h

    Zero point five six

    Zero point eight three

    Zero point seven five

    smoke

    Measured concentration

    Mg/Nm3

    Nine point five

    Nine point six

    Nine point eight

    Conversion concentration

    Mg/Nm3

    Twenty-five point nine

    Twenty-five point one

    Twenty-three point five

    Emission

    Kg/h

    Zero point one eight

    Zero point one nine

    Zero point one seven

    Exhaust volume

    Nm3/h

    Six thousand eight hundred and twenty-eight

    Seven thousand five hundred and forty-four

    Seven thousand one hundred and two

    oxygen content

    %

    Sixteen point six

    Sixteen point four

    Sixteen

    Smoke temperature

    Centigrade

    Fifty-two

    Fifty-two

    Fifty-one

    Chimney height

    M

    Twenty

    Chimney diameter

    M

    Zero point four

    Remarks: converted emission concentration = measured emission concentration * (21- reference oxygen content) / (21- measured oxygen content).

    The reference oxygen content (%) of coal fired boiler is 9.


    Unorganized exhaust gas detection results

    Detection point

    time

    Detection project

    Particulate matter (mg/m3)

    For the first time

    The second time

    Third time

    Factory area

    2017.12.4

    Upwind to 1#

    Zero point one six

    Zero point one three

    Zero point one five

    Downwind to 2#

    Zero point two two

    Zero point one nine

    Zero point two two

    Downwind to 3#

    Zero point one nine

    Zero point two one

    Zero point two one

    Downwind to 4#

    Zero point one eight

    Zero point one seven

    Zero point two one


    Export test results of sewage treatment station

    Date of detection

    frequency

    Detection project

    CODCr

    BOD5

    SS

    ammonia nitrogen

    PH

    2017.12.04

    For the first time

    Forty-three point one

    Six point three

    Fourteen point eight

    Seven point seven

    Seven point one

    The second time

    Forty point two

    Five point six

    Fifteen point six

    Six point eight

    Seven point one

    Third time

    Thirty-nine point six

    Five point one

    Thirteen point nine

    Seven point three

    Seven point two

    Fourth times

    Forty-one point six

    Five point three

    Fourteen point eight

    Seven point one

    Seven point one

NEWS CENTER

伟信医药

GREAT INNOVATION PHARMA


Address : No.588 Zixing  Road,Zizhu National High-tech Industrial Development Zone, Minhang , Shanghai China
Zip code: 200241
Tel:8621-51143139 / 31229518  
Fax:8621-57747216 / 69517800
Website:www.gipharma.com.cn 
E-mail:sales@gipharma.com.cn

Copyright © 20011-2016,www.gipharma.com.cn ,All rights reservedCopyright © GIP Group Co., Ltd. strictly prohibit copying words without permission.